WM5-96
Function Description
Figure A
The sign of measured quant-
ity and output quantity re-
m
ains the same. The output
quantity is proportional to the
measured quantity.
Input and output scaling capability. Working of the analogue outputs (y) versus input variables (x)
Figure B
The sign of measured quant-
ity and output quantity
changes simultaneously. The
output quantity is proportion-
al to the measured quantity.
Figure C
The sign of measured quant-
ity and output quantity re-
mains the same. On the
range X0...X1, the output
quantity is zero. The range
X1...X2 is delineated on the
entire output range Y0 =
Y1...Y2 and thus presented in
strongly expanded form.
Figure F
The sign of the measured
quantity remains the same,
the one of the output quantity
changes as the measured
quantity leaves range X0...X1
and passes to range X1...X2
and vice versa.
Figure E
The sign of the measured
quantity changes but the one
of the output quantity
remains the same. The output
quantity steadily increases
from value X1 to value X2 of
the measured quantity.
Figure D
The sign of measured quant-
ity and output quantity re-
m
ains the same. With the
measured quantity being
zero, the output quantity
already has the value
Y1 = 0.2 Y2.
Live zero output.
0 50 A 100 A
0 10 mA 20 mA
-100 kW 0 100 kW
-5 mA 0 +5 mA
80 V 100 V 120 V
0 5 mA 10 mA
0 50 A 100 A
4 12 mA 20 mA
-100 kW 0 100 kW
0 10 mA 20 mA
0
50 A 100 A
-5 mA 0 +5 mA
Insulation between inputs and outputs
Meas. /digi
-
tal inputs
Relay
output
Open collec
-
tor output
Analogue out.
10V, 20mA
Analogue out.
±5mA
AR1034 AR2040 AR1039
Power Supply
90-260VAC/DC
Power Supply
18-60VAC/DC
Meas. /digital
inputs
- 4kV 4kV 2kV 2kV 4kV 2kV 4kV 4kV 4kV
Relay output
4kV 4kV (*) 4kV 4kV 4kV 4kV 4kV 4kV 4kV 4kV
Open coll.out.
4kV 4kV 4kV (*) 4kV 4kV 4kV 4kV 4kV 4kV 4kV
Analogue out.
10V, 20mA
2kV 4kV 4kV 4kV (*) 4kV 4kV 4kV 4kV 4kV 4kV
Analogue out.
±5mA
2kV 4kV 4kV 4kV 200V (**) 4kV 4kV 4kV 4kV 4kV
AR1034
4kV 4kV 4kV 4kV 4kV - - 4kV 4kV 4kV
AR2040
2kV 4kV 4kV 4kV 4kV - - 4kV 4kV 4kV
AR1039
4kV 4kV 4kV 4kV 4kV 4kV 4kV - 4kV 4kV
90-260VAC/DC
4kV 4kV 4kV 4kV 4kV 4kV 4kV 4kV - -
18-60VAC/DC
4kV 4kV 4kV 4kV 4kV 4kV 4kV 4kV - -
NOTE: In case of fault of first insulation the current from the measuring inputs to the ground is lower than 2 mA.
(*) The given insulation is granted among outputs plugged in different slots. The modules equipped with two or four outputs
have therefore non insulation among the outputs. (**) Insulation between the 2 outputs of the same module is 200V for 1 min.