Specifications are subject to change without notice WM5 96 DS ENG 210708 3
WM5-96
Number of analogue inputs
Current 1 (1-phase; system code: 3)
3
(3-phase; system code: 3)
Voltage 1 (1-phase; system code: 3)
4 (3-phase; system code: 3)
D
igital inputs (on request)
U
p to 12
AQ1038 No. of inputs: 3 (voltage-free)
Purpose “dmd” measurements
synchronisation.
T
ariff selection: energy.
Contact status reading.
Clock synchronisation.
Contact measuring current
<8mA/ 17.5 to 25VDC
AQ1042
Number of inputs: 3 +
excitation
output
Purpose “dmd” measurements
synchronisation.
Tariff selection: energy.
Contact status reading.
Clock synchronisation.
Excitation output 16V<+Aux<24VDC Max 15mA
Contact measuring current
15mA
Common characteristics
Close contact resistance Max 1kΩ
Open contact resistance Min 100kΩ
Insulation see “Insulation between
inputs and outputs” table
Accuracy
(display, RS232, RS485) In: 5A, If.s.: 10A
Un: see voltage ranges below
Current (A
L1
, A
L2
, A
L3
) from 0.05In to Imax:
(@20°C ±5°C, R.H. ≤75%) ±(0.2%RDG+2DGT)
from 0.01In to 0.05In:
±(0.5%RDG+2DGT)
Current (A
n
) ±0.5% RDG (0.2 to 2 In)
@ 40 to 100 Hz
Voltage (@20°C±5°C,R.H.≤75%)
range
A
V5: 400/690V
L-L
AC
V
L-N
: 185 V to 460 V
V
L-L
: 320 V to 800 V
±
(0.2%RDG+1DGT)
range AV6: 120/208V
L-L
AC
V
L-N
: 45 V to 145 V
V
L-L
: 78 V to 250 V
±(0.2%RDG+1DGT)
Includes also:
fr
equency
, power supply
and output load influences
Fr
equency ±
0.1% RDG (40 to 440 Hz)
Active power and 0.05In to Imax, PF 1:
apparent power ±(0.5%RDG+1DGT)
(@ 20
°
C
±
5
°C, R.H. ≤ 75%) 0.01In to 0.05In, PF 1:
±(1%RDG+1DGT)
0.1In to Imax, PF0.5L, PF 0.8C:
±(0.6%RDG+1DGT)
0.02In to 0.1In,PF0.5L, PF 0.8C:
±
(1%RDG+1DGT)
Reactive power
(@ 20°C ± 5°C, R.H. ≤ 75%) 0.1In to Imax,
sen
ϕ 0.5L/C:
±
(2%RDG+1DGT)
0.05In to 0.1In, sen
ϕ 0.5L/C:
±
(2.5%RDG+1DGT)
0.05In to Imax,
sen
ϕ 1: ±(2%RDG+1DGT)
0.02In to 0.05In,
sen
ϕ 1: ±(2.5%RDG+1DGT)
Energies
(@ 20°C ± 5°C, R.H. ≤ 75%) Active: class 0.5 according
to
EN62053-22, ANSI C12.20
R
eactive: class 2 according
to EN62053-23, ANSI C12.1
In: 5A, Imax: 10A
0.1In: 500mA,
S
tart-up current: 5mA
Un:
400/690V
L-L
(AV5)
Un:
120/208V
L
-L
(AV6)
Harmonic distortion 1% FS (FS: 100%)
(@ 20
°
C ± 5°C, R.H. ≤ 75%)
phase:
±
2°; Imin: 5mA
RMS
;
I
max: 15Ap; Umin: 30V
RMS
;
Umax: 500Vp
T
emperature drift
≤
200ppm/°C (A/V), ≤300ppm/°C
(all the other measur
ements)
Sampling rate
6400
samples/s
@ 50Hz
7680
samples/s
@ 60Hz
Display Graph LCD backlighted
(128x64 dots). Read-out for
the instantaneous variables:
4x4 digit
Total energies: 4x9 digit;
Partial energies: 4x9 digit
Display refresh time 100ms
Max. and min. indication Max. 9999 (999,999,999),
Min. -9999 (–999,999,999)
Front LED Red
Blinking light in case of vir-
tual alarm
Fixed light in case of digital
output activation (alarm)
Measurements Current, voltage, power,
energy, power factor, frequen-
cy, harmonic distortion (see
“Display Pages”). TRMS
measurement of a distorted
wave (voltage/current) .
Coupling type
Dir
ect.
Cr
est factor
< 3, max 10A peak
Input impedance
400/690V
L-L
(AV5) 1.77 MΩ ±
5%
120/208V
L-L
(A
V6) 885 k
Ω ±
5%
Current ≤ 0.01Ω
Fr
equency
40
to
440 Hz
Overload protection (max values)
Continuous voltage/current AV5: 460V
LN
, 800V
LL
/10A
AV6: 145V
LN
, 250V
LL
/10A
For 500ms: voltage/current AV5: 800V
LN
, 1380V
LL
/36A
A
V6: 240V
LN
, 416V
LL
/36A
Input specifications
Kommentare zu diesen Handbüchern