CARLO GAVAZZI WM5-96 - PROGRAMMING Bedienungsanleitung Seite 7

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 17
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 6
Specifications are subject to change without notice WM5 96 DS ENG 210708 7
WM5-96
AC/DC voltage 90 to 260V (standard)
18 to 60V (on request)
Power consumption 30VA/12W (90 to 260V)
20VA/12W (18 to 60V)
Supply specifications
Pulse voltage (1.2/50µs)
EN61000-4-5
Safety standards IEC60664, IEC61010-1
EN60664, EN61010-1
M
easurement standards
I
EC60688, EN60688,
EN62053-22, EN62053-23,
ANSI C12.20, ANSI C12.1
Approvals CE, cURus and CSA
C
onnections 5(6) A
S
crew-type
m
ax. 2.5 mm
2
w
ires (2x 1.5mm
2
)
Max. screws tighteinig torque:
0.5 Nm
Housing
Dimensions 96x96x140 mm
Material ABS,
self-extinguishing: UL 94 V
-0
Protection degree Front: IP65, NEMA4x,
NEMA12
Weight Approx. 600 g
(packing included)
Operating -10° to +45°C (14° to 113°F)
t
emperature
(
R.H. < 90% non-condensing)
Limit range of operating temp. -20° to +55°C (-4° to 131°F)
(
R.H. <90% non-condensing)
Storage temperature -30° to +60°C (-2to
1
40°F)
(
R.H. < 90% non-condensing)
Installation category III
Pollution degree 2
A
ltitude
u
p to 2000m (6560 feet) above
s
ea-level
Insulation reference
voltage 300 VRMS to ground (AV5 input)
Dielectric strength 4kVAC
RMS
(for 1 min)
Noise Rejection
CMRR
100 dB, 48 to 62 Hz
EMC
Emissions EN61000-6-3, EN60688
residential environment,
commerce and light industry
Immunity EN61000-6-2
industrial envir
onment.
ANSI/IEEE C37.90-1989
(surge, withstand and fast
transient test)
General Specifications
Revenue approval settings
The access to the pr
ogramming parameters via front key pad and/or serial commu-
nication ports is locked.
The front key pad (up and down keys) allows the displaying of the variables only
,
while the communication ports allows the transmission of the variables only
.
A proper “instrument settings” form must be filled up by the user before equipment
supplying.
WM5-96 is supplied with the desired modules plugged and sealed in the proper slots.
WM5-96 fulfils: the ANSI/IEEE C12.20-1998 requirements;
the CAN3-C17-M84 r
equirements;
and can be certified accor
ding to:
C12.20-1998, class 0.5 (independent labs);
AE-0924 Industry Canada Approval.
In this case ther
e ar
e 2 base configurations:
1. display module + measuring input module
AV5 3 + power supply module H.
2. display module + measuring input module
AV6 3 + power supply module H.
Seitenansicht 6