Specifications are subject to change without notice WM5 96 DS ENG 210708 1
Class 0.2 (current/voltage)
ARM
®
powered
Back-lighted graph display (128x64 dots)
Bargraph indication of instantaneous power (kW sys)
Front size: 96x96 mm
Measurement of single phase and system instantaneous
variables: W, var, VA, PF,
VLL, VLN, A
L
,
A
n
, Hz, THD, ASY
V
LL, ASY VLN (for all measurements max, min, dmd/AVG
and max dmd/AVG values)
Measured energies (imported/exported): kWh and kvarh
Current and voltage inputs with autoranging capability
4x4 DGT instantaneous variable read-out
4x9 DGT total energies read-out
4x9 DGT partial energies read-out
Energy measurements according to ANSI C12.20, CA 0.5,
EN62053-22 CL 0.5S and ANSI C12.1, EN62053-23 CL 2
4
total 3-phase, 48 partial 3-phase and 12 total single
phase independent energy meters to be used as sin-
gle, dual, multi-time tariff management
Display refresh rate: 10 time / sec
Harmonic distortion analysis (FFT) up to the 63
rd
harmonic
with graphic and numeric indication (current and voltage)
Harmonics source detection
Data stamping of up to 10,000 events: alarm, min,
max, digital input status, digital output status as
remote control, resets
4 independent communication ports:
optical front communication port (ANSI C12.18)
optional RS 422/485 serial port,optional RS232 + real
time clock function, optional Ethernet port
Product Description
3-phase utility grade power
quality analyzer. Particularly
recommended for the mea-
surement of the main electri-
cal variables.
Housing for panel mounting,
with optical communication
Energy Management
Modular Smart Power Quality Analyzer
Type WM5-96
M
ODBUS RTU and TCP, JBUS protocol, iFIX SCADA
compatibility
Real time clock function (without back-up)
Up to 12 optional digital inputs (sync function, remote
digital input control)
Up to 16 optional digital outputs (pulse, alarm, remote
control)
16 fr
eely configurable alarms with OR/AND logic link-
able with up to 4 relay outputs and up to 16 open collec-
tor outputs
Up to 8 optional analogue outputs (+20mA, +10VDC,
+/- 5mA)
Universal power supply
: 18-60VAC/VDC, 90-260 VAC/VDC
Front protection degree: IP 65, NEMA4x, NEMA12
How to order
WM5-96 see next page
port (according to the ANSI
standards), RS485/RS232 or
Ethernet communication
ports, pulse and alarm out-
puts. Parameters program-
ming and data reading by
means of Wm5Soft.
How to order
Wm5Soft
Parameters programming and data reading by means of
Wm5Soft.
Description Part N. Slot A Slot B Slot C Slot D Slot E
WM5-96 base with ANSI local port AD2001
WM5-96 base without local port AD2000
Power supply (18-60VAC/DC) AP1021
Power supply (90-260VAC/DC) AP1020
Measuring input (AV5: 400/690VL-L) AQ2030
Measuring input (AV6: 120/208VL-L) AQ2031
RS485 port (9 600 bps) AR1034 1-port
RS485 port (115,200 bps) AR2040 1-port
Ether
net/Internet port
AR1061 1-port
Analogue output (20mA DC) AO2050 2-out 2-out
Analogue output (10V DC) AO2051 2-out 2-out 2-out 2-out
Analogue output (+/-5mA DC) AO2052 2-out 2-out 2-out 2-out
Relay output AO1058 1-out 1-out 1-out 1-out
Relay output AO1035 2-out 2-out
Open collector output AO1059 1-out 1-out 1-out 1-out
Open collector output AO1036 2-out 2-out 2-out 2-out
Open collector output AO1037 4-out 4-out 4-out 4-out
Digital inputs AQ1038 3-in 3-in 3-in 3-in
Digital inputs + Aux AQ1042 3-in 3-in 3-in 3-in
RS232 port + RTC (9 600 bps) AR1039 1-port
Modules Combination
Seitenansicht 0
1 2 3 4 5 6 ... 16 17

Inhaltsverzeichnis

Seite 1 - Type WM5-96

Specifications are subject to change without notice WM5 96 DS ENG 210708 1• Class 0.2 (current/voltage)• ARM®powered• Back-lighted graph display

Seite 2 - How to order WM5 96

10 Specifications are subject to change without notice WM5 96 DS ENG 210708WM5-96System variablesEquivalent three-phase voltageVoltage asymmetryT

Seite 3 - Input specifications

Specifications are subject to change without notice WM5 96 DS ENG 210708 11WM5-96Analogue outputs (all listed variables with the only exception o

Seite 4 - Output specifications

12 Specifications are subject to change without notice WM5 96 DS ENG 210708WM5-96Display variables in three-phase systems, 4-wire connectionsNo

Seite 5 - Software functions

Specifications are subject to change without notice WM5 96 DS ENG 210708 13WM5-96WM5-96WM5-96L1L2L3291018CT connection (3-wire system)Direct conn

Seite 6 - Time period management

14 Specifications are subject to change without notice WM5 96 DS ENG 210708WM5-96Wiring diagrams (cont.)3-phase, 3-wire input connections - Unbal

Seite 7 - Revenue approval settings

Specifications are subject to change without notice WM5 96 DS ENG 210708 15WM5-96WM5-96WM5-96RS422/485 NOTE: additional devices provided with RS4

Seite 8 - Alarm parameters and logic

16 Specifications are subject to change without notice WM5 96 DS ENG 210708WM5-96ARMPoweredPRGmeasuresSSR!RALWM5-96SmartPowerQuality Analy

Seite 9 - Function Description

Specifications are subject to change without notice WM5 96 DS ENG 210708 17WM5-96WM5-96WM5-96WM5-96ModulesAP102118-60VAC/DC power supplyAP102090-

Seite 10 - Accuracy

Description Ch Part No. Legend2 Specifications are subject to change without notice WM5 96 DS ENG 210708WM5-96Range code+sys (meas. inputs)400/69

Seite 11

Specifications are subject to change without notice WM5 96 DS ENG 210708 3WM5-96Number of analogue inputsCurrent 1 (1-phase; system code: 3)3(3-p

Seite 12 - Display pages

4 Specifications are subject to change without notice WM5 96 DS ENG 210708WM5-96Analogue Outputs (on request)Number of outputs Up to 8 (max 4 x 2

Seite 13 - Wiring diagrams

Specifications are subject to change without notice WM5 96 DS ENG 210708 5WM5-96Data stampingType of data Alarm, min, max, digital input status,

Seite 14 - Wiring diagrams (cont.)

6 Specifications are subject to change without notice WM5 96 DS ENG 210708WM5-96Analysis principle FFTHarmonic measurementCurrent Up to the 63rdh

Seite 15 - CONVERTER

Specifications are subject to change without notice WM5 96 DS ENG 210708 7WM5-96AC/DC voltage 90 to 260V (standard)18 to 60V (on request)Power co

Seite 16 - Dimensions

8 Specifications are subject to change without notice WM5 96 DS ENG 210708WM5-96Alarm parameters and logicON alarm (SET 1)OFF alarm (SET2)Up alar

Seite 17 - (+mA)(-V)(+mA)(-V)

Specifications are subject to change without notice WM5 96 DS ENG 210708 9WM5-96Function DescriptionFigure AThe sign of measured quant-ity and ou