PQA700 is a complete power quality analyzer suitable to
check the electrical phenomena according to what is
required by the EN50160 Standard (Harmonics, Supply
voltage dips, Supply voltage variations and Supply
interruptions). The basic features are particularly interesting
because they include: a display which, thanks to its shape,
shows the information clearly and neatly; a built-in impact
dot matrix printer for printing the measurement results
manually and automatically; a rechargeable battery to
allow the user to take measurements even under tough
disturbances and special power supply conditions; an
RS232 communication port to download and process the
measurements adequately and last but not least an easy
and intuitive operating mode.
Base accuracy 0.5% RDG (current, voltage)
Measurement of single phase and system variables: V, A,
W, VA, var, TPF, DPF, Hz, Wh, varh-L, varh-C, VAh
Complete Harmonic analysis up to the 50th harmonic
20ms continuous signal sampling
Automatic storage of MIN, MAX and AVG values
Time-based curve distribution of variable and load
Statistic management of stored variables
Oscilloscope functions
Built-in printer
RS232 port
Rechargeable battery
Complete accessory set
Carrying case
Analysis software
All this is supplied together with a rich equipment of
accessories including a set of three accurate clamp-on
probes which allows to take measurements up to 1200A
(with two selectable full scales: 100A or 1000A) a complete
set of cables, an analysis software. On request a 3000A
flex clamp probe is available
(model: Flex3000Q). And
finally a modern and rugged
carrying case. The compact
dimensions, the rugged
construction, the shape and
the reduced weight of the
instrument simplify its use
and its location under any
condition of installation.
PQA700
Starting from 1994 with the publication of the EN50160
Standard by CENELEC, the idea of quality of the electric
service has been introduced and made executive for the
public electrical network at low and medium voltage.
This event underlines, for the first time, the necessity to
introduce some measuring parameters of the electric
product, with the indication of its basic features and the limits
within which it is considered as a quality product. The items
featuring the service/product in the origin of the installation
are the following: its waveform, its frequency, its magnitude
and symmetry (in a three-phase system); the relevant
conditions are: normal use and emergency use.
It is clear that the characteristics of the electric product not
only depend on the skill of the supplier in the electrical
network management, but also on how the electric product is
used. The improvement in the quality of the electric service
obviously implies a cost both for the supplier and for the
user. The supplier’s costs can be summed up in the
updating, extension and development of the electrical
network; the user’s costs: any necessary disturbance
compensation, any necessary subordinate electric
connection, any possible payment of penalties due to a low
power factor or to the overcoming of the limits of power
demand. Some additional costs can be even higher and
unforeseeable, such as those due to failures of the loads and
to the subsequent unplanned maintenance of the machines
and of the installations merely due to electric problems.