Hardware Functions
In-Out
Performances
The best to suit your needs!
Power Analyzers WM12 DIN WM12 96
107.5x90mm (WM12 DIN) (6 DIN mod.)
96x96mm (WM12 96)
LED
YES
3 DGT
N.A.
W-VA:±(1% F.S.+1DGT)
var:±(2% F.S. +1DGT)
V
LL: ±(1.5% F.S. +1DGT)
VLN-A:±(0.5% F.S. +1DGT)
200ppm/°C
1.5 sample/s
unbalanced: 1-2-3-phase
100/208VAC, 400/660VAC
5AAC
N.A.
Prog.: CT up to 5000A, VT up to 10kV
TRMS method
Sys:V
LL,VLN,An,VA,VAdmd,Wdmd, Wdmd peak,Hz
single-phase:VLL,VLN,A,VA, W, var,PF
N.A.
N.A.
N.A.
N.A.
RS422/485 (Modbus)
Action: on variables and outputs
Over neutral current or under and over
voltage indication (warning signal)
24, 48,115, 230VAC; 18 to 60VDC
CE, cURus (cCSAus only WM2 96)
IP40 (WM12 DIN) IP65 (WM12 96)
Housing (H x W)
Display type
Variables on display
Instantaneous variables
Energy variables
Accuracy
Temperature drift
Sampling rate
System type
Voltage inputs (Un)
Current inputs (In)
Digital inputs
Primary of CT/VT
Measurements:
Variables
Harmonic distortion
Outputs: Pulse
Alarm
Analogue
Serial
Digital filter
Other characteristics
Power supply
Approvals
Protection degree
WM12 DIN and WM12 96 are general purpose multi func-
tion meters that allow to monitor all the mains parameters
of an electrical line or load. The compact housings com-
bined with a complete selection of measurements allow the
instruments to be mounted in all the switch and control
gears as local indicators, instead of the classical single
function analogue or digital panel meters.
The unit is provided with some unique installation visual
status functions like:
the window control of the mains 3-phase voltage
notifying the user at a glance if the mains is supplied
out of the requested power supply tolerance,
the neutral current control showing immediately anyload
or installation anomaly due to high harmonic distortion
or load insulation loss (high earth leakage current).