CARLO GAVAZZI EN61036 Betriebsanleitung Seite 5

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 18
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 4
8
ENGLISH
9
ENGLISH
NOISE REJECTION (CMRR): 100dB, 48 to 62 Hz
EMC: EN 50 081-2, EN 50 082-2
OTHER STANDARDS:
Safety requirements: IEC 61010-1, EN 61010-1
Product requirements: IEC 60688-1, EN 60688-1,
Energy measurements: EN61036, EN61268.
Pulse outputs: DIN43864
CONNECTIONS:
Screw-type, max. wire section: 1.5 mm
2
x 2 or 2.5 mm
2
x 1
HOUSING:
Dimensions: 96 x 96 x 140mm; Materials: ABS; self-extinguishing: UL 94 V-0
DEGREE OF PROTECTION: Front: IP 65
WEIGHT: 600 g approx. (packing included)
HARMONIC DISTORTION ANALYSIS
ANALYSIS PRINCIPLE: FFT
HARMONIC MEASUREMENT:
Current: Up to the 50
th
harmonic
Voltage: Up to the 50
th
harmonic
TYPE OF HARMONICS:
THD (VL1);THD odd (VL1); THD even (VL1) and also for the other
phases: L2 and L3.
THD (AL1); THD odd (AL1); THD even (AL1) and also for the other
phases: L2 and L3.
HARMONIC PHASE ANGLE:
The instrument measures the angle between the single harmonic of
"V" and the single harmonic of "A" expressed as " ° ", making it possible
to know if the harmonics are generated or imported.
Note: if the system is a 3-wire type, the angle cannot be measured.
HARMONIC DETAILS: For every THD page it is possible to see the
harmonic order.
DISPLAY PAGES: The harmonic contents is displayed as a graph
showing the whole harmonic spectrum.
The information is given also as numerical information:
THD in % / RMS value; THD odd in % / RMS value; THD even in %
/ RMS value; Single harmonic in % / RMS value
OTHERS: The harmonic distortion can be measured both in 3-wire or
4-wire systems. Tw: 0.02 s
ENERGY MANAGEMENT
TIME PERIODS:
Selectable: single time, dual time and multitime.
SINGLE TIME:
Number of energy meters:
total: 4 (9 digits); partial: 4 (7 digits)
DUAL TIME:
Number of energy meters:
total: 4 (9 digits); partial: 8 (6 digits)
Time periods: 2, programmable within 24 hours
MULTI-TIME:
Number of energy meters:
total: 4 (9 digits); partial: 48 (6 digits)
Time periods: 4, programmable within 24 hours
Time seasons: 3, programmable within 12 months