• Data format: 1 start bit, 8 data bit, no parity, 1 stop bit
• Baud-rate: 9600 bauds
• Protocol: MODBUS (JBUS)
• Other data: as per RS485/RS422
DIGITAL OUTPUTS: (on request)
the working of the pulse, alarm or pulse/alarm outputs is fully program-
mable and is independent from the chosen output module.
PULSE OUTPUT: (on request)
• Number of outputs: Up to 4 (on request)
• Type: From 1 to 1000 programmable pulses for k-M-G Wh, k-M-G
varh, open collector (NPN transistor).
• VON 1.2VDC / max. 100mA; VOFF 30VDC max.
• Pulse duration: 220ms (ON),
≥220ms (OFF)
according to DIN43864.
• Insulation:
By means of optocouplers, 4000 Vrms output to measuring
inputs, 4000 Vrms output to supply inputs.
• Note: The outputs can be either open collector type or relay type (for
this latter one see the characteristics mentioned in the ALARMS)
ALARMS: (on request)
• Number of setpoints: up to 4, independent
•
Alarm type: Up alarm, down alarm, up alarm with latch, down alarm
with latch, phase asymmetry/phase loss, neutral loss.
• ON set-point adjustment: 0 to 100% of the electrical scale.
• OFF set-point adjustment: 0 to 100% of the electrical scale (hysteresis
is given by ON-OFF or OFF-ON).
• On - time delay: 0 to 255s
• Relay status: selectable, normally de-energized, normally energized.
• Output type: relay, SPDT; AC 1-8A, 250VAC; DC 12-5A, 24VDC; AC
15-2.5A, 250VAC; DC 13-2.5A, 24VDC
•
Min. response time: ≥ 150ms, filter excluded, setpoint On-time delay: 0
• Insulation: 4000 Vrms output to measuring input, 4000 Vrms output to
power supply input.
• Note: the outputs can be either relay type or open collector type (for this
latter one, see the characteristics mentioned in the PULSE OUT-
PUTS).
SOFTWARE FUNCTIONS
PASSWORD: Numeric code of max. 3 digits;
• 2 protection levels of the programming data.
• 1st level: Password "0", no protection
• 2nd level: Password from 1 to 499, all data are protected.
MEASUREMENT SELECTION: see the relevant table.
TRANSFORMER RATIO:
For CT up to 30000A, For VT up to 600kV.
SCALING FACTOR
Operating mode:
• Electrical scale: compression/expansion of the input scale to be
connected to up to 4 analogue outputs and up to 4 alarm outputs.
• Electrical range: Programmable within the whole measuring range.
DIGITAL FILTER:
• Filter operating range: 0 to 99.9% of the input electrical scale
• Filtering coefficient: 1 to 255
• Filter action: alarms, analogue and serial outputs (fundamental
variables: V, A, W and their derived ones).
EVENT LOGGING: Only with the RS232 + RTC module. The max./min.
values of the selected variables and the alarm status are stored with
reference to date (dd:mm:yy) and time (hh:mm:ss). Max. capacity: 480
events.
PAGE VARIABLES: 4 variables per page; up to 27 variable pages one
of which is completely programmable.
POWER SUPPLY SPECIFICATIONS
AC VOLTAGE:
18 - 60 VDC/AC; 90-260 VDC/AC
POWER CONSUMPTION:
≤30VA / 12W (90-260V); ≤20VA / 12W (18-60V)
GENERAL SPECIFICATIONS
OPERATING TEMPERATURE:
0 to +50°C (R.H. <90% non-condensing)
STORAGE TEMPERATURE:
–10 to +60°C (R.H.<90% non-condensing).
INSULATION REFERENCE VOLTAGE:
600 VRMS to ground
INSULATION: 4000 VRMS between all inputs/outputs to ground
DIELECTRIC STRENGTH: 4000 VRMS for 1 minute