Useful Information
Installation
15
Serial port
18
21
21
What is ASY
The ASY variable allows the user to control the symmetry
of the delta voltages (for systems without neutral) and star
voltages (for systems with neutral). The variable is calculat-
ed according to the following formula:
Where: Vmax is the max. value among VL1-N, VL2-N, VL3-N
Vmin is the min. value among VL1-N, VL2-N, VL3-N
Vavg is the average: (VL1-N, VL2-N, VL3-N)/3
The variable is not displayed by the instrument, but it can be
retransmitted by the analogue or RS422 / 485 output and
can be controlled by means of the alarm.
Retransmitted Variables
N° Variable Three-phase Three-phase Note
with neutral without neutral
1 V L-NΣ x Σ = system
2 V L-LΣ xxΣ = system
3WΣ xxΣ = system
4 varΣ xxΣ = system
5VAΣ xxΣ = system
6PFΣ xxΣ = system
7 THD V x x
if FFT activated
8 THD A x x
if FFT activated
9A n x
10 VA dmd x x
11 W dmd x x
12 ASY x x asymmetry
13
All the instantaneous variables (powers, currents, voltages)
Vmax - Vmin
Vavg
*100ASY=
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]