Seitenansicht 6
6
To begin with
tot-Prd
4
8
8
The energy meter pages are different according to the set-
ting of the instrument (see energy meter menu on pag.13).
If you choose “tot” the instrument displays:
Generated capacitive reactive
energy: integration of the sum of
single phase reactive powers of
quadrant 4 only.
Consumed capacitive reactive
energy: integration of the sum of
single phase reactive powers of
quadrant 2 only.
Generated inductive reactive
energy: integration of the sum of
single phase reactive powers of
quadrant 3 only.
Consumed inductive reactive
energy: integration of the sum of
single phase reactive powers of
quadrant 1 only.
Generated active energy: integra-
tion of the sum of single phase
negative active powers only.