Specifications are subject to change without notice WM24-96DS0403 3
WM24-96
Alarm outputs (on request)
Number of outputs up to 2, independent
Alarm type Up alarm, down alarm
Variables to be controlled see the List of the
variables that can be
connected...”
Set-point adjustment from 0 to 100% of the
electrical scale
Hysteresis from 0 to 100% of the
electrical scale
On-time delay 0 to 255s
Relay status Selectable; normally
de-energized and normally
energized
Output type Relay, SPDT type
AC 1-8A @ 250VAC
DC 12-5A @ 24VDC
AC 15-2.5A @ 250VAC
DC 13-2.5A @ 24VDC
Min. response time 150ms, filters escluded,
Set-point on-time delay: “0 s”
Insulation By means of optocouplers,
4000 V
RMS
output to
measuring input,
4000 V
RMS
output to
supply input.
Note The outputs can be either
relay type or open collector
type (for the open collector
output refer to the specifica-
tions described in the “pulse
outputs”)
Output Specifications (cont.)
Page Variables Up to 4 by page
Three-phase system with neutral Page 1: V L1, V L2, V L3,
V LN
Page 2: AL1, AL2, AL3
Page 3: W L1, W L2, W L3
Page 4: VA L1, VA L2
VA L3
Page 5: var L1, var L2,
var L3
Page 6: PF L1, PF 2,
PF L3, PF
Page 7: W , var ,
PF , Hz
Page 8: W , VA ,
PF , Hz
Page 9: W dmd, VA dmd
Energy, gas, water,
meter pages See Energy, gas, water meter
settings” table
Password Numeric code of max
4 digits; 2 protection levels
of the programming data
1st level Password “0”, no protection
2nd level Password from 1 to 1000, all
data are protected.
Transf ormer ratio CT from 1 to 5000
VT from 1.0 to 1999, where
CT x VT 10000
Power demand (dmd)
Integration time Programmable from 1 to 30 min
Filter
Filter operating range From 0 to 100% of the
input electrical scale
Filtering coefficient 1 to 16
Filter action Measurements, alarms, serial
port (fundamental variables:
V, A , W a n d t h e i r d e r i v e d o n e s ) .
Software Functions
AC voltage 90 to 260 VDC/VAC
18 to 60VDC/VAC
24 VAC -15+10% 50-60Hz
48 VAC -15+10% 50-60Hz
115VAC -15+10% 50-60Hz
230 VAC -15+10% 50-60Hz
Power consumption 30VA/12W (90 to 260V)
20VA/12W (18 to 60V)
Supply Specifications
Gross Automation (877) 268-3700 · www.carlogavazzisales.com · [email protected]